Design Sheet: LPZ 1 to LPZ 2/3 – SDB & DB Protection Criteria

By Tokai Engineering | Tech Team |

15 May 2025

Compliance with IEC 62305-4 and IEC 61643-11

1. Objective

To provide effective surge protection for Sub-Distribution Boards (SDB) and Distribution Boards (DB) by mitigating residual surges transmitted from upstream surge protection devices, as per IEC 62305-4. This applies at the LPZ 1 to LPZ 2/3 boundary.

  

2. Surge Protection Device (SPD) – TMP 320/4

 

Parameter Value
Nominal Voltage (Un) 400/230 V AC (3P+N+PE)
Maximum Continuous Voltage (Uc) 275 V AC
Maximum Discharge Current (Imax) 40 kA (8/20 µs) per mode
Voltage Protection Level (Up) < 1.5 kV (L-N, N-PE)
Response Time ≤ 25 ns
Disconnection Mechanism ≤ Thermal fuse + window indicator
Remote Indication Contact ≤ Yes, Isolated Form C
Compliance ≤ IEC 61643-11:2011, CE Mark

 

3. Smart Monitoring System – TLSMS/03

Feature Description
Surge Event Counter Lightning strike count with timestamp
Surge Amplitude Logging Measured energy of each surge (kA)
SPD Status Monitoring Real-time SPD health tracking
Grounding Resistance Monitoring Detects grounding path status
Voltage Anomaly Detection ≤ Over/under voltage alerts
Communication Interface ≤ RS-485 (Modbus protocol)
Integration ≤ Compatible with BMS, SCADA, cloud
Certifications ≤ KEMA Certified, IEC 61643-11 compliant

4. Compliance & Risk Management Notes

This design fulfills the LPZ 1 to LPZ 2/3 boundary protection requirement of IEC 62305-4 by using the TMP 320-4 Type 2 SPD for surge reduction, combined with TLSMS/03 for diagnostics and operational awareness. This ensures protection for downstream sensitive equipment such as computers, servers, and control panels, while enhancing maintenance scheduling and system uptime visibility.